What types of fire equipment are there?
You are here: Home » News » Industry News » What types of fire equipment are there?

What types of fire equipment are there?

Views: 129     Author: Site Editor     Publish Time: 2022-12-11      Origin: Site

Inquire

facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button

Every year, fire departments in the United States respond to more than 1.3 million fires that collectively cause over 15 billion dollars in direct property damage. Behind each of those incidents lies a common thread: the presence—or absence—of correctly selected, installed and maintained fire equipment. From a compact handheld extinguisher in a server closet to a full scale foam deluge system protecting an oil refinery, the choices are vast, technical and highly regulated. Understanding which category of fire equipment fits which hazard is no longer a niche concern reserved for fire protection engineers; it is a core procurement, risk management and compliance decision that every facility manager, safety officer and building owner must master.

Fire equipment falls into five functional categories: (1) detection and alarm systems that identify fires and warn occupants, (2) passive fire protection products that limit fire spread through construction, (3) active suppression systems that extinguish or control fire, (4) portable firefighting appliances that first responders or occupants can deploy immediately, and (5) emergency communication and lighting that guide safe evacuation.

Within each category, dozens of subtypes, technologies and installation standards compete for budget and attention. An office tower may need addressable smoke detectors, photoluminescent exit signs, wet pipe sprinklers and Class K extinguishers in its cafeteria, while a lithium battery warehouse demands early warning air sampling, clean agent suppression and thermal barriers. The following sections dissect every major class of fire equipment, explain how each is tested and listed, and provide decision tables to help match the right technology to the hazard.

Table of Contents

  1. Detection and Alarm Systems

  2. Passive Fire Protection Products

  3. Active Suppression Systems

  4. Portable Firefighting Appliances

  5. Emergency Communication and Lighting

  6. Inspection, Testing and Maintenance Requirements

Detection and Alarm Systems

Detection and alarm systems sense heat, smoke or flame, then send audible, visual or data signals to occupants and monitoring stations; they range from single station smoke alarms to multi loop addressable panels tied to cloud based monitoring.

Modern life safety codes recognize four primary detection technologies. Ionization smoke alarms use a small radioactive source to ionize air between two plates; when smoke particles disrupt the current, the alarm triggers. They respond fastest to fast flaming fires with small smoke particles, such as those produced by burning paper or flammable liquids. Photoelectric smoke alarms employ a light source and a photosensor; smoke entering the chamber scatters the light onto the sensor. They excel at detecting smoldering fires typical of modern upholstery or overheated PVC wiring. Fixed temperature heat detectors activate when the ambient temperature reaches a preset threshold—commonly 135 °F or 194 °F—making them ideal for kitchens or garages where steam or exhaust would cause nuisance alarms. Rate of rise heat detectors trigger when the temperature increases faster than 12–15 °F per minute, catching rapidly developing fires before the absolute temperature threshold is reached.

Advanced systems integrate these sensors into addressable fire alarm control panels (FACPs). Each device reports a unique identifier, allowing technicians to pinpoint the exact location of an alarm. Analog addressable detectors go further by transmitting real time sensor values, enabling drift compensation and early warning before the alarm threshold is breached. Large campus style facilities may deploy air sampling or aspirating smoke detection (ASD) systems that draw air through pipes to a central laser chamber, achieving detection 30–1,000 times faster than spot type detectors. For high value data centers, very early smoke detection apparatus (VESDA) can identify incipient combustion before visible smoke appears, triggering staged responses such as local investigation, pre action sprinkler priming or clean agent release.

Selection criteria can be summarized in the following decision matrix.

Hazard TypeRecommended DetectorNFPA StandardTypical Coverage RadiusMaintenance Interval
Office cubiclesPhotoelectric spotNFPA 7221 ftAnnual sensitivity test
Commercial kitchenFixed temp heatNFPA 7215 ftSemi annual calibration
Server farmVESDA air samplingNFPA 76100 ft via pipeQuarterly filter check
Woodworking shopRate of rise heatNFPA 7215 ftSemi annual test
Archive storagePhotoelectric beamNFPA 7260 ft beam spanAnnual alignment check

Passive Fire Protection Products

Passive fire protection products are built into the structure and include fire rated walls, floors, doors, dampers, penetration seals and intumescent coatings that compartmentalize fire and maintain structural integrity without human intervention.

Fire resistance ratings, expressed in hours (e.g., 1 hour, 2 hour), are determined by standardized tests such as ASTM E119 or UL 263, where assemblies are exposed to a time temperature curve reaching 1,000 °F at 5 minutes and 2,000 °F at 4 hours. Fire rated gypsum wallboard assemblies achieve 1 to 4 hour ratings by layering type X or type C gypsum and mineral fiber insulation. Fire doors are classified as A (3 hour), B (1.5 hour) or C (0.75 hour) and must be self closing and positive latching. Fire dampers installed in HVAC ducts prevent fire spread through air handling systems; they are tested under UL 555 and must close within 15 seconds upon fusible link activation at 165 °F or 212 °F.

Cable and pipe penetrations are a frequent weak point. Firestop systems use intumescent sealants, fire rated mortars or mechanical devices that expand when exposed to heat, sealing voids created by melting plastic conduits or insulation. Intumescent thin film coatings applied to structural steel can add 1–3 hours of fire resistance by swelling up to 50 times their original thickness, insulating the steel from critical temperatures above 1,100 °F. Below grade parking structures often rely on fire rated concrete or board encasement systems to maintain load bearing capacity during a prolonged fire.

A practical specification checklist for passive products is as follows.

Building ElementTest StandardRequired RatingCommon MaterialsKey Installation Check
Exit stairwell wallASTM E1192 hour2x type X gypsum each sideFull height to deck
Mechanical shaftUL 5551.5 hourFire damper + sleeveFusible link orientation
Floor ceiling assemblyASTM E1192 hourConcrete + spray applied fireproofingThickness verification
Steel columnUL 2633 hourIntumescent coatingDry film thickness

Active Suppression Systems

Active suppression systems discharge water, foam, gas or dry chemicals to suppress or extinguish a fire; the main types are wet pipe, dry pipe, pre action, deluge, foam water, gaseous clean agent and water mist systems, each governed by specific NFPA standards.

Wet pipe sprinkler systems are permanently filled with water under pressure and are the default choice for offices, hotels and retail spaces. When a sprinkler head fuses at its rated temperature (typically 155 °F), water flows immediately. Dry pipe systems employ pressurized air in the pipes, releasing water only after the air pressure drops when a head opens. They are essential for unheated warehouses or parking garages to prevent freezing. Pre action systems add a detection step; a fire alarm must first trigger a solenoid valve to flood the pipes, reducing accidental discharge in data centers or museums. Deluge systems use open nozzles and a separate detection system to flood an entire zone simultaneously, protecting high hazard areas like aircraft hangars or transformer yards.

Foam water sprinkler systems generate aqueous film forming foam (AFFF) or alcohol resistant foam (AR AFFF) to blanket flammable liquid fires, preventing reignition. They are common in petrochemical refineries and fuel storage depots. Clean agent systems such as FM 200, Novec 1230 or inert gases like IG 541 suppress fire by reducing oxygen or interrupting the combustion chain reaction without damaging electronics. Water mist systems discharge fine droplets less than 1,000 microns in diameter, cooling flames and displacing oxygen while using 50–90 % less water than traditional sprinklers—ideal for heritage buildings or cruise ships.

Selection parameters include hazard classification, water supply adequacy, environmental regulations and clean up considerations.

System TypeHazard ClassNFPA StandardWater Demand (gpm)Discharge DurationTypical Use Case
Wet pipeLight hazardNFPA 1315–3030 minOffice building
Dry pipeOrdinary hazardNFPA 1325–5030 minUnheated warehouse
Pre actionHigh value electronicsNFPA 13Variable30 minData center
DelugeExtra hazardNFPA 15500–1,00010 minAircraft hangar
Foam waterFlammable liquidNFPA 16Variable10 min foam + 30 min waterFuel depot
Clean agentClass C hazardsNFPA 2001None10 min holdServer room
Water mistHeritage or marineNFPA 75010–2530 minMuseum gallery

Portable Firefighting Appliances

Portable firefighting appliances consist of handheld or wheeled extinguishers, fire blankets and small hose reels that occupants can deploy immediately; they are classified by the type of fire they extinguish (A, B, C, D, K or F) and the extinguishing agent used.

Water extinguishers (Class A) cool burning materials and are suitable for wood, paper and textile fires. Foam extinguishers (Class A and B) form a blanket over flammable liquids, preventing vapor release. Carbon dioxide (Class B and C) extinguishers displace oxygen and leave no residue, making them ideal for electrical switchgear. Dry chemical extinguishers interrupt the combustion chain reaction and are versatile (Class A, B, C), but leave corrosive powder requiring cleanup. Wet chemical extinguishers (Class K) spray a fine mist that reacts with cooking oils to form a soapy layer, used in commercial kitchens. Clean agent extinguishers use Halotron or FE 36 for Class C fires in data centers. Fire blankets smother small clothing or cooking fires and are mandatory in laboratories handling flammable solvents.

Selection and placement follow the “fire triangle” principle—fuel, heat, oxygen—and the travel distance rule in NFPA 10. Light hazard occupancies require extinguishers within 75 ft travel distance; ordinary hazard within 50 ft; extra hazard within 30 ft. Mount extinguishers on brackets or in cabinets 3.5–5 ft above floor level so the handle is accessible to persons with disabilities. Provide signage that identifies the extinguisher class and pictograms showing the types of fires for which it is approved. Annual maintenance includes pressure checks, pull pin inspection and hydrostatic testing every 5 or 12 years depending on cylinder material.

Emergency Communication and Lighting

Emergency communication and lighting encompass voice evacuation systems, mass notification platforms, exit signs and egress lighting that remain operable during power failures, ensuring occupants receive clear instructions and can safely exit.

Emergency voice alarm communication (EVAC) systems override background music and provide staged messages such as “Investigate alarm on Floor 3” followed by “Evacuate Floor 3 only.” They must meet intelligibility standards (0.7 Common Intelligibility Scale) and provide 24 hours of standby power plus 15 minutes of alarm operation. Mass notification systems (MNS) extend beyond fire events to include severe weather, active shooter or hazardous material releases, integrating SMS, email, desktop alerts and outdoor giant voice speakers.

Exit signs must be visible from any point in an exit access corridor and must remain illuminated for at least 90 minutes after power loss. LED exit signs consume 90 % less energy than incandescent and last 10–25 years. Egress lighting must provide 1 footcandle average and 0.1 footcandle minimum along the path of egress. Central battery systems can power multiple fixtures, while self contained units use internal nickel cadmium or lithium batteries. Photoluminescent exit signs absorb ambient light and glow for hours without electrical power, ideal for retrofit applications.

Inspection, Testing and Maintenance Requirements

All fire equipment must be inspected, tested and maintained on a defined schedule under NFPA 25 for water based systems, NFPA 72 for detection and alarm, NFPA 10 for extinguishers and NFPA 101 for emergency lighting, with digital documentation to prove compliance.

Inspections are visual checks—verifying gauge pressures, ensuring access is unobstructed, confirming LED indicators are illuminated. Testing involves functional operation—flowing water from sprinkler inspectors test connection, activating smoke detectors to verify alarm transmission, or conducting 90 minute battery discharge tests on emergency lighting. Maintenance includes replacement or overhaul—recharging extinguishers, recalibrating detectors, hydrostatic testing cylinders. Frequencies range from weekly (control valves) to quarterly (sprinkler alarm devices) to annual (full detector sensitivity tests) to five yearly (internal sprinkler pipe inspection).

A digital CMMS (Computerized Maintenance Management System) streamlines the process by automatically scheduling tasks, recording completion dates and generating compliance reports. QR coded asset tags allow technicians to scan and update status in the field. Failure to maintain equipment can void insurance coverage or lead to OSHA citations; therefore, assign a designated Fire Safety Manager with budget authority and executive reporting responsibilities.

Summary

From the smallest ionization smoke alarm to a 5,000 gpm foam deluge monitor, fire equipment forms an integrated ecosystem designed to detect, contain and extinguish fire while protecting life and property. Understanding the five functional categories—detection, passive protection, active suppression, portable appliances and emergency communication—empowers facility managers to match technology to hazard, comply with evolving codes and deliver quantifiable risk reduction. Regular inspection, testing and continuous improvement convert capital expenditures into perpetual safety performance, ensuring that when the next alarm sounds, the outcome is controlled and the loss is minimal.


Subscribe To Our Newsletter​​​​​​​

We are looking for the area sells agency to sell our products. If you have interest please contact us.

Incorrect E-mail
Leave a Message
Get In Touch